Ope03

OPE03 is a MULTI-FUNCTION INPUT SELECTION ERROR

On each inverter there are a series of inputs to the inverter. S1 and S2 are normally used for the rotation of the inverter being CW and CCW. The remaining inputs S3 on up are programmable in the inverter as to what that input means to the inverter.
If you have two inputs both programmed as the same input in the inverter memory, you will get this fault. The same function can not come from two different inputs.

CSH 01-15-09
Last updated: 01/15/2009 / Node ID: 1608 / Key Chain: 12.1.74.645.648.